Earth fault loop impedance

Maximum Zs and route length from device and cable.

Table 8.1 maximum Zs and a Paragraph B5.2 route-length check for copper conductors up to 120 mm², using a measured Ze or the 80% Zs assumption. Cable inductance, aluminium conductors and RCD-only protection are not modelled.

Rated operating current of the protective device.

Circuit-breaker type or fuse. Sets the Table 8.1 maximum Zs.

Clause 5.7.2: 0.4 s for circuits supplying socket-outlets up to 63 A, hand-held Class I or portable equipment. Table 8.1 gives 5 s values for fuses only.

One-way route length of the final subcircuit, for the Paragraph B5.2 route check.

Copper active conductor, up to 120 mm² (Paragraph B5.2.2). Resistance uses the working-temperature resistivity.

Protective earth conductor cross-sectional area.

External earth fault-loop impedance measured at, or provided for, the origin of the circuit. Leave blank to assume 80% of nominal voltage at the protective device (Paragraph B5.2.1(b)).

Results

Select device rating, type, and disconnection time, then calculate.

Method and assumptions

  • Maximum Zs is from AS/NZS 3000:2018 Table 8.1. Circuit-breaker values are 230 V ÷ (k × In) with the mean tripping multiples of Paragraph B4.5 (Type B 4, Type C 7.5, Type D 12.5). Table 8.1 gives 5 s values for fuses only.
  • Clause 5.7.2: 0.4 s for final subcircuits supplying socket-outlets up to 63 A, hand-held Class I or portable equipment; 5 s for other circuits where people are not exposed to unsafe touch voltages.
  • The route check uses Paragraph B5.2 with copper conductors at 22.5 × 10⁻³ Ω·mm²/m. With a measured Ze, Zs = Ze + Zint is compared with Table 8.1. Without one, Zint is limited to 80% of Zs (Equation B7), which reproduces the Table B1 route lengths.
  • Verify by testing the installed circuit (Clause 8.3.9).

For guidance only. Verify against the current AS/NZS 3000 and your fault-loop design.

Common questions

Where do the maximum Zs values come from?

AS/NZS 3000:2018 Table 8.1, which gives the maximum earth fault-loop impedance for the whole circuit including the supply, at 230 V. For circuit-breakers the value is 230 V ÷ (k × In) using the mean instantaneous tripping multiples of Paragraph B4.5: 4 for Type B, 7.5 for Type C and 12.5 for Type D. Fuse values are taken from Table 8.1.

Which disconnection time applies, 0.4 s or 5 s?

Clause 5.7.2 requires 0.4 s for final subcircuits supplying socket-outlets rated up to 63 A, hand-held Class I equipment, or portable equipment moved by hand during use. Other circuits may use 5 s where people are not exposed to unsafe touch voltages. Table 8.1 gives 5 s values for fuses only.

How is the maximum route length worked out?

With Paragraph B5.2 of AS/NZS 3000. The circuit impedance uses copper resistivity at working temperature, 22.5 × 10⁻³ Ω·mm²/m. If you enter a measured Ze, Ze plus the circuit impedance is compared with Table 8.1. If not, the circuit impedance is limited to 80% of Zs (Equations B6 and B7), which reproduces the route lengths in Table B1.

Does an RCD change the result?

No. The calculator checks disconnection by the circuit-breaker or fuse against Table 8.1. RCDs required under Clause 2.6.3 are additional protection and are not used to relax the Table 8.1 values here.

Check the stated method and limits against your installation. Results are calculation aids, not certification.