Cable sizing

Compare copper V-75 sizes for current capacity, installation conditions and voltage drop.

Copper V-75 multicore screening using explicit cable construction, ampacity columns and correction factors; simplified Table C8 voltage drop. Aluminium/XLPE sizing is withheld pending verified data. A result is not a certified cable selection.

Copper conductor · V-75 insulation (75 °C thermoplastic)

Maximum sustained load current in amperes.

One-way cable run length in metres.

Permitted voltage drop as a percentage of supply voltage.

Single-phase uses 230 V; three-phase uses 400 V supply.

How the cable is installed affects its current-carrying capacity.

Selects the applicable insulation column of Table 3.15 or 3.18. Short covered lengths require installation-specific data.

Air or soil temperature used for tabulated ambient derating.

Number of circuits bunched together (grouping factor).

Harmonics and short-circuit check Kh 1 · No short-circuit check

User-supplied design allowance. This does not analyse neutral current or derive the correct harmonic factor.

Optional. Enables adiabatic short-circuit size check.

Protective device clearing time for adiabatic check.

Results

Complete the required inputs, then press Calculate.

Method and assumptions

Copper V-75 screening with two loaded cores for single phase and three for balanced three phase. Governing size considers ampacity (after ambient/grouping/burial/soil/harmonics), volt-drop, and optional adiabatic short-circuit. Confirm against your licensed edition and manufacturer data before use. Wall/conduit grouping assumes bunched, equally loaded circuits; tray means one horizontal perforated row. Partial insulation follows clause 3.4.3; complete insulation covers more than 400 mm along the cable. Underground grouping and parallel runs require a separate assessment.

Base ampacity reference (V-75)

AS/NZS 3008.1.1:2025 Table 3.15 (two loaded cores). Air: 40 °C. Ground: 25 °C, 0.5 m depth, 1.2 K·m/W. These base values precede correction factors and assume no thermal insulation.

Size (mm²)Conduit in air (A)Clipped to wall (A)Buried direct (A)
1131422
1.5161828
2.5232640
4303452
6394465
10526087
166880114
2590107147
35112131178
50133159211
70170201259
95204248311

Read the copper V-75 cable sizing and voltage-drop guide for supported methods, assumptions and examples.

Common questions

What does this cable sizing tool check?

Copper V-75 multicore current-carrying capacity from AS/NZS 3008.1.1:2025 Tables 3.15 and 3.18 with the applicable correction factors, voltage drop by AS/NZS 3000 Table C8, and an optional adiabatic short-circuit check. It does not select protective devices or confirm the installation complies.

How does it handle thermal insulation?

It uses the partially or completely surrounded current rating columns rather than a single derating factor. Under clause 3.4.3 of AS/NZS 3008.1.1, completely surrounded means bulk insulation around the cable for more than 400 mm; 150 mm to 400 mm counts as partially surrounded. Shorter covered lengths need installation-specific data.

Does spacing cables on a tray remove the grouping factor?

Not always. The tray option assumes one horizontal row on perforated tray and uses Table 3.35. Three circuits spaced one cable diameter apart still take a 0.98 correction factor. Other tray types, layers or arrangements need their own factors.

What does the short-circuit check assume?

The adiabatic equation S = I√t ÷ K with copper V-75 conductors from 75 °C to 160 °C (K = 111.2) and clearing times up to 5 s. Cable restraint, the protective device’s let-through energy and the actual cable construction need separate checks.

Check the stated method and limits against your installation. Results are calculation aids, not certification.

Calculator guidanceNew calculator emails

Calculation model 2026-11-02.1